Back to top

How To Select Earthing Cable Size !!exclusive!! May 2026

[ S = \frac\sqrtI^2 \times tk ]

Selecting the wrong earthing cable size can lead to equipment damage, fire, or fatal electric shock. The earthing conductor must be sized to safely carry fault current long enough for the overcurrent device (breaker or fuse) to trip. how to select earthing cable size

Copper, PVC insulated, ( I = 5000A ), ( t = 0.2s ) [ S = \frac\sqrtI^2 \times tk ] Selecting

How to Select the Correct Earthing Cable Size (Step-by-Step Guide) Step 3: Follow Simplified Table (BS 7671 /

[ S = \frac\sqrt5000^2 \times 0.2115 = \frac\sqrt25,000,000 \times 0.2115 = \frac\sqrt5,000,000115 = \frac2236115 \approx 19.4 \text mm^2 ] → Select copper cable. Step 3: Follow Simplified Table (BS 7671 / IEC) If you don’t want to calculate, use this simplified copper earthing conductor size relative to the phase conductor:

| Conductor material | PVC insulation (70°C) | XLPE (90°C) | Bare copper | |-------------------|----------------------|-------------|-------------| | Copper (Cu) | 115 | 143 | 226 | | Aluminum (Al) | 76 | 94 | 148 |

| Phase conductor area (mm²) | Min. copper earthing conductor (mm²) | |----------------------------|---------------------------------------| | ≤ 16 | Same as phase conductor | | 25 – 35 | 16 mm² | | 50 – 95 | 25 mm² | | 120 – 150 | 35 mm² | | 185 – 240 | 50 mm² | | ≥ 300 | 70 mm² |

Copyright © 2026 SENDITUR